507.3 FunctionsScreen 5.7 Inch Color LCD and Interface with Touch PanelPattern Max 100 , Available to operate each channel's patternSegment Max 2,400 ( Max 100 per segment)Waiting Mode Setup per pattern and setup of using or not using per segmentRepetition & Connection Available to use Pattern Repetition and Section Repeat Loof Setup(Max. 20) Free connecting operation among patterns is availablePID Group Each channel 4 Zones, Selectable between manual or automaticControl Method Heating control or Heating/Cooling control in each channel. PID orON/OFF controlAuto Tuning Optimal PID GAIN is automatically calculated according to Set Value.It could be operated by each channelProportional Band 0.0 ~ 1000.0 ℃ ( If "0" = On/Off control, Not "0" = PID control)Integral Time 0 ~ 6000 sec ( "0" = No Integral Calculation)Differential Time 0 ~ 6000 sec ( "0" = No Differential Calculation)ON/OFF control Available to select Dead zone 0.1 ~ 1000.0 ℃Event Log Max 40 Event Logs could be saved depend on various situationsLCD protection Back light will be off according to designated time of not using touch panelPassword Password is available to prevent other people from changing system setupProtection of Over-Integral and Differential ARW Zone setup ( 50 ~ 200 % of proportional band)Fuzzy Function Control overshootRAMP Available to select SV changing ratio in case of fixing operationRestrict MV changing ratio Function to control sudden change of MVAlarm Setup 4 points, High, Low, Deviation etc. 20 kindsInner Signal 8 points, object, range and delayed time setup are availableTime Signal 8 points when program mode operationGraph Function PV, SV of each channel could be display by graphFixing Operation Hour Available to set fixing operation hour upReservation OperationFuction Available to use reservation operation time by using built in timer.User Logo Display User logo could be shown for 3 sec after power on. Download throughcommunication portScreen Capture Upload is available through communication portLanguage Korean and EnglishContact Input RUN/STOP, STEP, HOLD and Error Input(Stop operation, Delayed/ setup is available)Contact Output Output of various signalsStorage in Power Failure Various setting and operation information memoryReturn from Power Failure STOP / COLD / HOT return when power failure is restoredکﺮه ﻫﺎﻧﯿﺎﻧگ ﻣﺤﺼﻮﻻت اﻧﺤﺼﺎری ﻤﻧﺎﯾﻨﺪه ﺳﯿﻮان رشکﺖ021-33989001www.sivancarno.com021-33989002