355.1 Operation Setup5 Function SetupPressing [MENU] button on the operation screen gets into setup menu where various parameters canbe set.When [OPERATION SETUP] button is pressed on the function setup screen, the operation setupscreen is displayed.- Operation Type : Program control or fixed control- Limit SV change rate : used to prevent rapid SV changes during fixed control operation.- Limit MV change rate : Setup when concerned about problems caused by rapid changesin controlled output. When it is set, the output rate is limited to 10 % persecond (5 % per 0.5 sec).- Fixed operation time : if this time is set, when the time expires during fixed control operation,the operation stops automatically.- Power-out Handling : If power goes down and recovers, the type of operation is set.STOP ->Operation stopped state, COLD-> Control from beginning, HOT-> control from the stopped point- Buzzer Setup : Touch sound, ON/OFF- Touch Input Lock : When set, only [MENU] and [NEXT] respond. Prevents mistakes.- Automatic Screen Power Down : To preserve lifespan of LCD and BACK LIGHT, when there are noinputs for certain period of time, the screen powers downautomatically. {Does not affect the operation}- Purging : Suppresses over shoot. {Time taken to reach the intended value delays}کﺮه ﻫﺎﻧﯿﺎﻧگ ﻣﺤﺼﻮﻻت اﻧﺤﺼﺎری ﻤﻧﺎﯾﻨﺪه ﺳﯿﻮان رشکﺖ021-33989001www.sivancarno.com021-33989002