41- Input Compensation : When the product is shipped, it is adjusted to precision with error marginwithin 0.1 %. However, in case of imprecision during simultaneous usewith other instruments, the input temperature can be increased/decreased byforce within the range of ±100 ℃.- Filter Setup : If severe noise is present in the sensor signal system, and measured values areinconsistent, then suitable filtering time should be set.(Higher this value, the prompt control become difficult).- Control Mode : Heating control, heating/cooling control selection- Control output type : SCR, SSR, RELAY Selection.(When relay is selected, relay number selection box is activated).- Anti Reset Wind-up : Range setup to prevent overloading.(Setup in P-BAND Percentage)- Output Frequency : If control ouput type is SSR or RELAY (PID Control), PID control willbe carried out in time ratio. Setup output frequency at this time.(Shorter the frequency, control performance is better, but can stress relay etc.Recommend SSR usage)- ON/OFF Control Irresponsiveness : At ON/OFF control, setup output switch Irresponsiveness. Ifirresponsiveness is high, the control performance degrades,low irresponsiveness stresses the relay etc through frequent6.2 Control/Transmission Setupکﺮه ﻫﺎﻧﯿﺎﻧگ ﻣﺤﺼﻮﻻت اﻧﺤﺼﺎری ﻤﻧﺎﯾﻨﺪه ﺳﯿﻮان رشکﺖ021-33989001www.sivancarno.com021-33989002