LED105CODE No. Setting Mode LED104CODE No. Setting Function FactorysettingOutdoor unit RemarksMaster Slave2 8 Prohibited0 0 Prohibited lSetting prohibited0 1 Prohibited2 9 Prohibited0 0 Prohibited lSetting prohibited0 1 Prohibited3 0 Energy savinglevel setting0 0 Level 1 (stop) l¡ -*1The capacity limit can beselected by the externalinput terminal (CN133) whenoperating with the “EnergySaving Peak Cut function.”The lower the level, the morethe effect of energy saving, butthe cooling/heating performancewill also drop.0 1 Level 2 (operated at40% capacity)0 2 Level 3 (operated at60% capacity)0 3 Level 4 (operated at80% capacity)0 4 Level 5 (operated at100% capacity)3 2 Prohibited0 0 Prohibited lSetting prohibited0 1 Prohibited0 2 Prohibited3 3 Prohibited0 0 Prohibited lSetting prohibited0 1 Prohibited4 0Capacitypriority setting(in low noisemode)0 0 Off (quiet priority) l¡ -*1If the cooling/heatingperformance becomesinsufficient when the low noisemode is set, it is possible toset “capacity priority” thatautomatically cancels the lownoise mode (once performanceis restored, the mode willautomatically return to the lownoise mode).0 1 On (capacity priority)4 1 Low noisemode setting0 0 Off (Normal) l¡ -*10 1 On (Low noise mode)4 2Low noisemodeoperation levelsetting0 0 Level 1 l¡ -*1Level1: The operating soundlowers from about 3 to 5 dB(A)more than the rated valueLevel2: The operating soundlowers from about 3 to 5 dB(A)more than the Level10 1 Level 2*1: Do not set this for outdoor units with Slave setting.- (07-65) -FUNCTIONSETTINGFUNCTIONSETTING