SYSTEM SETTING1.SYSTEM TYPE SETTING1-1. Set the DIP switch to the corresponding system type as shown in the table.Do not use a nonexistent switch combination.NotePerform the system setting and address setting , before turning on the power.¾For the air conditioner to operate properly, perform the correct setting.¾OUTDOOR UNIT SETTINGSet the outdoor unit address settingSet the number of slave unitSet the number of outdoor units installedRefrigerant circuit address settingTerminal resistor settingFunction settingSet the DIP SW SET3-3 & 3-41 : SET3-3 OFF, SET3-4 OFF : Master x 12 : SET3-3 OFF, SET3-4 ON : Master x 1 Slave x 13 : SET3-3 ON , SET3-4 OFF : Mater x 1, Slave x 2Set the DIP SW SET5-1 & 5-21 : SET5-1 OFF, SET5-2 OFF : Number of 12 : SET5-1 OFF, SET5-2 ON : Number of 23 : SET5-1 ON , SET5-2 OFF : Number of 3Set the DIP SW SET3-1 & 3-2Master : SET3-1 OFF, SET3-2 OFFSlave 1 : SET3-1 OFF, SET3-2 ONSlave 2 : SET3-1 ON , SET3-2 OFFSETTING FOR MASTER UNIT & SLAVE UNIT.SETTING FOR MASTER UNIT & SLAVE UNIT.SETTING FOR MASTER UNIT & SLAVE UNIT.SETTING FOR MASTER UNIT & SLAVE UNIT.SETTING FOR MASTER UNIT ONLY.( . . . Factory Setting)Set the Rotary SW REF AD x10 & x1See the switch detail for "1-2. Address setting"Set the DIP SW SET5-4See the switch detail for "1-6. Terminal resistorsetting"Indoor unit connection checkSee the detail for "1-7 Indoor unit connection check"(This function is available J-II and J-IIS series)(This function is available VR-II, V-IIand V-III series)(This function is available VR-II, V-IIand V-III series)(This function is available VR-II, V-IIand V-III series)- (07-01) -FUNCTIONSETTINGFUNCTIONSETTING