PM 1001484 000 08 Device handbook SINEAX DM5000 65/969. Technical dataInputsNominal current: adjustable 1...5 A; max. 7.5 A (sinusoidal)Measurement category: 300V CAT IIIConsumption: ≤ I2 x 0.01 Ω per phaseOverload capacity: 10 A continuous100 A, 5 x 1 s, interval 300 sNominal voltage: 57.7…400 VLN (UL: 347VLN ), 100...693 VLL (UL: 600VLL );Measurement max.: 520 VLN , 900 VLL (sinusoidal)Measurement category: 600V CAT IIIConsumption: ≤ U2 / 1.54 MΩ per phaseImpedance: 1.54 MΩ per phaseOverload capacity: 520 VLN , 900 VLL continuous800 VLN , 1386 V LL, 10 x 1 s, interval 10sSystems: Single phaseSplit phase (2-phase system)3-wire, balanced load3-wire, balanced load, phase shift (2xU,1xI)3-wire, unbalanced load3-wire, unbalanced load, Aron connection4-wire, balanced load4-wire, unbalanced load4-wire, unbalanced load, Open-YNominal frequency: 42...50...58Hz or 50.5...60...69.5Hz, configurableSampling rate: 18 kHzMeasurement uncertaintyReference conditions: Acc. IEC/EN 60688, ambient 15…30°C,sinusoidal input signals (form factor 1.1107), no fixed frequency for sampling,measurement time 200ms (10 cycles at 50Hz, 12 cycles at 60Hz)Voltage, current: ± 0.1% 1) 2)Neutral current: ± 0.2% 1) (if calculated)Power: ± 0.2% 1) 2)Power factor: ± 0.2°Frequency: ± 0.01 HzImbalance U, I: ± 0.5%Harmonics: ± 0.5%THD U, I: ± 0.5%Active energy: Class 0.5S, EN 62053-22Reactive energy: Class 0.5S, EN 62053-24Measurement with fixed system frequency:General ± Basic uncertainty x (F config–F actual ) [Hz] x 10Imbalance U ± 2% up to ± 0.5 HzHarmonics ± 2% up to ± 0.5 HzTHD, TDD ± 3.0% up to ± 0.5 Hz1) Related to the nominal value of the basic quantity2) Additional uncertainty if neutral wire not connected (3-wire connections)• Voltage, power: 0.1% of measured value; load factor: 0.1°• Energy: Voltage influence x 2, angle influence x 2