Page 49 of 80Section 12:Sequence of Operation: DANGERELECTRICAL SHOCK HAZARDDisconnect electric before service.More than one disconnect switchmay be required to disconnectelectric from equipment.Equipment must always beproperly grounded.12.1 Unit ConfigurationBased on the unit's application, the unit may beconfigured in any number styles to achieve the describedfunctionality. Refer to the unit’s model number to seewhich configuration the unit was supplied with.12.2 Controls OptionsUnit may be controlled in one of the following ways:• Factory-mounted ALC controls (by factory)• Factory-mounted DDC controls (by others)• Factory-mounted terminal strip for field-mounted• Factory-mounted terminal strip for electromechanicalcontrols (by factory or by others)Unit Nomenclature Control Options:A = ALC, Standard Program, DOASB = ALC, Standard Program, RecirculatingC = ALC, Standard Program, DOAS with LOND = ALC, Standard Program, Recirculating with LONE = Controls by Others, Factory MountedF = Terminal Strip, Controls Provided and Mounted by OthersG = Remote ThermostatH = Compressor Lockout Thermostat12.2.1 Factory-Mounted ALC Controls(by factory)The ALC control option consists of a factory programmedcontroller and a series of factory-wired sensors. Thecontroller can operate in a 100% stand alone mode withthe use of a hand-held display. It can also connect toa building automation system (BMS) using one of fourcompatible protocols (BACnet®, LonWorks with theoptional Echelon card, Modbus, N2). The point mappingto these protocols can be pre-set, so that the protocol andbaud rates desired can be easily field-selected without theneed for additional downloads or technician assistance.Depending on the options ordered, remote sensors maybe installed and wired to the controller.12.2.2 Factory-Mounted DDC Controls(by others)Field-supplied DDC controls are mounted by the factoryper the customer’s specifications.12.2.3 Factory-Mounted Terminal Strip forField-Mounted DDC Controls (by others)Field-supplied DDC controls can be connected to thefactory-mounted and factory-wired terminal strip.12.2.4 Factory-Mounted Terminal Strip forRemote Thermostat(by factory or by others)A factory-supplied or field-supplied thermostat can beconnected to the factory-mounted and factory wiredterminal. The 24V factory-supplied thermostat has thefollowing capabilities:• Up to 4 heat/2 cool with humidity control -for heat pump• Up to 3 heat/2 cool with humidity control -for straight coolThe thermostat features a 45-90 °F [7-32 °C] temperaturecontrol range with a +/- 1 °F [0.5 °C] accuracy and arecapable of connecting to optional factory-supplied remoteindoor air and outdoor air temperature sensors.Figure 16: Equipment Touch DisplayRC/FC Series Installation, Operation, and Maintenance Manual