1MAC309294-MB F Section 7Measurement functionsRER620 397Technical Manual7.1.5.5 Monitored dataTable 349: VA, VB, VC Monitored data7.1.5.6 Technical dataTable 350: VA, VB, VC Technical dataName Type Values (Range) Unit DescriptionVAB-kV FLOAT32 0.00...4.00 xVn Measured phase to phase voltage amplitudephase ABVBC-kV FLOAT32 0.00...4.00 xVn Measured phase to phase voltage amplitudephase BVCA-kV FLOAT32 0.00...4.00 xVn Measured phase to phase voltage amplitudephase CV_INST_AB FLOAT32 0.00...4.00 xVn VAB Amplitude, magnitude of instantaneousvalueV_DB_AB FLOAT32 0.00...4.00 xVn VAB Amplitude, magnitude of reported valueV_RANGE_AB Enum 0=normal1=high2=low3=high-high4=low-lowVAB Amplitude rangeV_INST_BC FLOAT32 0.00...4.00 xVn VBC Amplitude, magnitude of instantaneousvalueV_DB_BC FLOAT32 0.00...4.00 xVn VBC Amplitude, magnitude of reported valueV_RANGE_BC Enum 0=normal1=high2=low3=high-high4=low-lowVBC Amplitude rangeV_INST_CA FLOAT32 0.00...4.00 xVn VCA Amplitude, magnitude of instantaneousvalueV_DB_CA FLOAT32 0.00...4.00 xVn VCA Amplitude, magnitude of reported valueV_RANGE_CA Enum 0=normal1=high2=low3=high-high4=low-lowVCA Amplitude rangeV_INST_A FLOAT32 0.00...4.00 xVn VA Amplitude, magnitude of instantaneous valueV_INST_B FLOAT32 0.00...4.00 xVn VB Amplitude, magnitude of instantaneous valueV_INST_C FLOAT32 0.00...4.00 xVn VC Amplitude, magnitude of instantaneous valueCharacteristic ValueOperation accuracy Depending on the frequency of the voltage measured: f n ±2Hz(Secondary PT voltages): At voltages range 0.01…1.15 X V n±0.5% or ±0.002 X V n(SIM0001/CVD): At voltages range 0.20 to 1.4 X V n±1% or ±0.005 X V nSuppression of harmonics DFT: -50 dB at f = n x fn , where n = 2, 3, 4, 5,…RMS: No suppression