Endura AZ30 series integral probe and remote transmitterCombustion oxygen monitor 8 HART®-Protocol80 COI/AZ30E–EN Rev. D8.5.2 Field Device Status Second ByteSecond Byte DescriptionBit #7 Field Device Malfunction A hardware error or failure has been detected by the device. Further information may be available through the Read Additional TransmitterStatus command.Bit #6 Configuration Changed A write command has been executed. A set command has been executed.Bit #5 Cold StartBit #4 More Status Available More Status information is available than can be returned in the Field DeviceStatus. Command #48 Read Additional Status Information provides thisadditional status information. Set if any of the device-specific status bits in command #48 are set.Bit #3 Primary Variable Analog Output Fixed The analog and digital analog outputs for the Primary Variable are held at therequested value. They do not respond to the applied process. Primary analog output set to a fixed value via HART (or via the HMI) putting thecurrent output into test mode.Bit #2 Primary Variable Analog Output Saturated The analog and digital outputs for the 'Primary Variable' are beyond their limitsand no longer represent the true applied process. Calculated Current Output 1 value is beyond the physical limits of the output.Bit #1 Non Primary Variable Out of Limits The temperature or cold junction cell voltage are beyond the operating limits ofthe probe. The Read Additional Transmitter Status command, #48, is required toidentify the variable. Set if SV, TV or QV sensor limit failure diagnostic bits are set.Bit #0 Primary Variable Out of Limits The measured oxygen value is beyond the operating limits of the probe. PV sensor out-of-limits diagnostic set.Table 8.5 Field Device Status Second Byte