Endura AZ30 series integral probe and remote transmitterCombustion oxygen monitor 6 Programming64 COI/AZ30E–EN Rev. D…Input/OutputCurrent Output 2 Displayed only if an option board is fitted.Elec. Range Hi Selects the electrical range high current output value.[0.00 to 22.00 mA]mA 20.00 mAElec. Range Lo Selects the electrical range low current output value.[0.00 to 22.00 mA]mA 4.00 mAOutput Failure When 'Enabled', the current output can be driven toa preset value if a Failure category diagnostic stateoccurs – see Section 9.2.1, page 84.DisabledEnabledDisabledFailure Current Sets a preset value that the current output is drivento when a Failure category diagnostic state is present– see page 83.Only available if Output Failure is Enabled.[0.00 to 22.0 mA]22.00 mAOutput #2 Test Selects % output levels for Current Output 2.When this parameter is exited, the current outputreturns to its normal operating value.[0, 25, 50, 75 or 100 %]0Parameter Comment / [Range] DefaultTable 6.12 Input/Output Menu (Continued)