ZP1-F Series Operation Manual 23Regulatory informationEuropean standards for fire control and indicating equipmentThese control panels have been designed in accordance with European EN 54-2,EN 54-4, BS 5839-1, NBN S 21-100, and NEN 2535 standards.In addition, all models comply with the following EN 54-2 optional requirements:Table 7: EN 54-2 optional requirementsOption Description7.8 Output to fire alarm devicesNote: Inputs and outputs on the optional 2010-1-SB expansion I/O board do notsupport the optional requirement of EN 54-2 clause 7.8 and should not be used forfire alarm devices.7.9.1 Output to fire alarm routing equipment [1]7.9.2 Alarm confirmation input from fire alarm routing equipment [1]7.10 Output to fire protection equipment (type A) [2]7.11 Delays to outputs7.13 Alarm counter [3]8.4 Total loss of the power supply8.9 Output to fault warning routing equipment [2]10 Test condition[1] Excluding two-zone models.[2] NEN 2535 operating mode only.[3] Dutch models only.EN 54-13 European compatibility assessment of system componentsThese control panels form part of a certified system as described by EN 54-13when installed and configured for EN 54-13 operation as described by themanufacturer in the corresponding installation documentation.Contact your installation or maintenance contractor to determine if your firesystem is compliant with this standard.European standards for electrical safety and electromagnetic compatibilityThese control panels have been designed in accordance with the followingEuropean standards for electrical safety and electromagnetic compatibility:• EN 60950-1• EN 50130-4• EN 61000-6-3• EN 61000-3-2• EN 61000-3-3