AC100 HIGH-PERFORMANCE VC INVERTER MANUAL INSTALLATION AND WIRING27Arrangement sequence of main circuit terminal with 132kW: Arrangement sequence of main circuit terminal with 160~560kWTerminal Symbol Name Function Definition(-) DC power terminal DC power output, (-) means DC bus cathode, (+) means DCbus anode, used for external braking unit.(+)(+) Braking resistance terminal Used for external braking resistance to realize quick stop.PBP1 DC reactor terminal Used for external DC reactor.(+)RInverter input terminal Used to connect 3-phase AC power supply.STUInverter output terminal Used to connect the motor.VWEarth Earth terminal, earth resistance<10ΩEChart 3-6:AC100 Series Inverter Main Circuit Terminals Array and Definition● 3-phase 380V Machine Main Circuit WiringModel Main Circuit TerminalsScrew SpecificationsSuggested Fixed Moment(N·m)Suggested Copper-coreCable Specification mm2(AWG)AC100-T3-R75G M4 1.2~1.5 1.5mm2(14)AC100-T3-1R5G M4 1.2~1.5 2.5mm2(12)AC100-T3-2R2G M4 1.2~1.5 2.5mm2(12)AC100-T3-004G M4 1.2~1.5 4mm2(10)AC100-T3-5R5G M4 1.2~1.5 6mm2(9)AC100-T3-7R5G M5 2~2.5 6mm2(9)AC100-T3-011G M5 2~2.5 10mm2(7)AC100-T3-015G M6 4~6 10mm2(7)AC100-T3-018G M6 4~6 16mm2(5)AC100-T3-022G M8 8~10 16mm2(5)AC100-T3-030G M8 8~10 25mm2(3)AC100-T3-037G M8 8~10 25mm2(3)AC100-T3-045G M8 8~10 35mm2(2)