Electrical installationClassic P3 60-150 A 01/2018 - V1 12CE-Advices4.3 CE-AdvicesThe devices adhere to the EU guidelines 89/336/EWG and the technical standards EN 61000-2and 61000-4 provided that the following conditions are observed:The device, the power choke, and the filter capacitors are mounted on a 500x500x2 mmmounting plate.The mounting plate must be connected to ground using a 10mm² wire.The motor housing must be connected to ground using a 10mm² wire.The device ground X1:8 must be connected to the mounting plate using a 2.5mm² wire.Device PE screw must be connected to the mounting plate using a 4mm² wire, l = 50mm.Connection:Power choke type: see technical detailsFilter capacitors: 3 x 0.5μF/600V∼ 3 x 1μF (x) + 1 x 0.5μF (y)Conductor length between the device and the power choke <250mmMotor connection:Motor conductors l = 1.5m, shieldedTacho and all control lines l = 1.5m, shieldedShielding connected to PEAssembly planManual-ZeichnungenE--P3-A917