9 01/2018 - V1 Classic P3 60-150 AElectrical installationConnection 4 Electrical installation4.1 ConnectionAuxiliary supply and field connectionsThe order of the connections to the screw terminals is obligatory.The input and output conductors may be altered or supplemented in accordance with theelectrical standards. All further advice is non-obligatory.The controllers are delivered with an auxiliary voltage input for 230 or 400V~(Please observe the type plate)Current consumption: 0.1AFuse F1 0.8A (5x20)Manuals-Zeichnungen-P3-A054-Hilfssp.The auxiliary voltage and the field supply areboth connected across the plug-in terminal X5.The phase position of the auxiliary voltage andthe power supply voltage do not have tocorrespond to each other.The field voltage amounts to210V= with a 230V~ connection andto 360V= with a 400V~ connection.Max. field current: 10AFeld fuse –F2, -F3 10AF (6.3 x 32)The field current has a watchdog.In case of a field failure the signal contact forthe field current opens.Contact for 24V / 1AThe LED for the field current lights when fieldcurrent flows.Manuals-Zeichnungen-P3-A054-Feld