E6581926F-1196[Parameter setting]Title Function Adjustment rangeReferenceof maximumvalue off677Defaultsettingf669 Logic output/pulse trainoutput selection (OUT)0: Logic output1: Pulse train output – 0f676 Pulse train output functionselection (OUT)0: Output frequency1: Output current2: Frequency command value3: Input voltage (DC detection)4: Output voltage (command value)5: Input power6: Output power7: Torque8: -9: Motor cumulative load factor10: Inverter cumulative load factor11: PBR (Braking resistor) cumulativeload factor12:Stator frequency13:VIA input value14:VIB input value15:Fixed output 1(output current 100% equivalent)16:Fixed output 2(output current 50% equivalent)17:Fixed output 3(Other than the output current)18:Communication data19: -20: VIC input value21, 22: -23: PID feedback valuefh185%fh150%150%185%185%250%-100%100%100%fh10 V10 V185%185%100%100.0%-20mA-100%0f677 Maximum numbers ofpulse train output 0.50-2.00 (kpps) – 0.80f678 Pulse train output filter 2-1000 (ms) – 64 Digital panel meter for referenceType: K3MA-F (OMRON)Connection terminal: OUT-E4, NO-E5Note 1: When item of f676 reaches “Reference of max. value”, the number of pulse train set by f677are sent to output terminals (OUT)Note 2: The ON pulse width is maintained constant.The ON pulse width is fixed at a width that causes the duty to reach 50% at the maximum pulsenumber set with f677.Therefore, the duty is variable.For example, the ON pulse width is approximately 0.6 ms when f677= 0.80 (pps)approximately 0.5 ms when f677= 1.00 (pps)approximately 0.3 ms when f677= 1.60 (pps)Note 3: The minimum pulse output rate is 10pps. Keep in mind that no pulses can be put out at any ratesmaller than this.Note 4: f676 = 12 is the motor drive frequency.