E65820569Procedure1. Setting of motor prameters(1) Set the Base frequency of motor to vl(Base frequency1).(2) Set the Base frequency voltage of motor to vlv(Base frequency voltage1).(3) Set the below motor parameters refer to name plate of motor and test report.VF-AS1, VF-PS1Title CommunicationNo. Functionf405 0405 Motor rated capacityf406 0406 Motor rated currentf407 0407 Motor rated rotational speedVF-S15, VF-FS1, VF-nC3Title CommunicationNo. Functionf405 0405 Motor rated capacityf415 0415 Motor rated currentf417 0417 Motor rated speedProcedure2. Connect the motor and perform the Auto-tuning(1) Set 4 to f400 (Auto-tuning).Some of the parameters will be calculated automatically. (VF-AS1, VF-PS1, VF-S15 only)(2) Set 2 to f400 (Auto-tuning).After setting, some of the parameters will be tuned to match the motor at the first operation.If the Auto-tunig error (etn、etn1~3) occurs at Auto-tuning, please refer to the countermeasure of the instructionmanual of each models.2.3. Toshiba IE3 motor parameter adaptation inverterThe default setting values of motor parameters of “VF-AS1/PS1/S15/nC3” have been changed to IE3 motors fromtraditional IE1 motors.Adaptation schedule is below.VF-S15 and VF-nC3: From Oct 2016VF-AS1 and VF-PS1: From Apr 2017The relation of the default setting values of motor parameters, applicable motors and the software version of inverter areshown in below table.Model Software version Applicable motor(Default setting value)Product version(Described in nameplate)VF-S15 V100 ~ V116 Traditional IE1 motor (0) ~ (8)V120 ~ IE3 motor (20) ~VF-nC3 V100 ~ V112 Traditional IE1 motor (0) ~ (7)V120 ~ IE3 motor (20) ~VF-AS1 V100 ~ V168 Traditional IE1 motor (0) ~ (17)V170 ~ IE3 motor (20) ~VF-PS1 V600 ~ V668 Traditional IE1 motor (0) ~ (12)V670 ~ IE3 motor (20) ~