E6581738④- 34 -VIA / VIC input value monitor is capable of reading the data from external devices in a range of 0.00 to100.00% (unsigned data: 0x0000 to 0x2710).VIB input value monitor is capable of reading the data from external devices in a range of -100.00 to100.00% (signed data: 0xD8F0 to 0x2710).If analog input mode is selected with the frequency setting mode selection parameter, however, keep inmind that any data entered via an analog terminal is regarded as a frequency command.VF-AS3RR input value: "Communication Number fe35"RX input value: "Communication Number fe36"II input value: "Communication Number fe37"These monitors can also be used as A/D converters irrespective of the inverter's control.RR / II input value monitor is capable of reading the data from external devices in a range of 0.00 to100.00% (unsigned data: 0x0000 to 0x2710).RX input value monitor is capable of reading the data from external devices in a range of -100.00 to100.00% (signed data: 0xD8F0 to 0x2710).If analog input mode is selected with the frequency setting mode selection parameter, however, keep inmind that any data entered via an analog terminal is regarded as a frequency command.7.5.14. fe14 (Cumulative run time)The operated cumulative time is read by the hexadecimal number.For example, when cumulative operation time is 18 hours, 0x12 (18 hours) is read.0x12 (Hex.) = 18 (Dec., hour)7.5.15. fe40 (Analog output (FM))fe41 (AM output monitor) (Only for the VF-AS3)The output value of FM/AM terminal is read.The value range is set to 0 to 10000 (0x2710).For example, when FM/AM output value is 50.00%, 0x1388 (Hex.) is read.0x1388 (Hex) = 50.00 (Dec %)* If the parameter f681 (Analog output) is set to 0, FM output monitor cannot be used.Please set 1 or 2 to f681.