E65821624. Selection and installation of peripheral devices 4-2Wire size for HD ratingWire size for ND ratingVoltageclassApplicablemotor (kW) Inverter type-formWire size (mm2 )Power circuitDC wireBrakingresistor(Optional)Ground-ing wireInput Output3-phase480 V0.4 VFAS3- 4004PCE 1.5 1.5 2.5 1.5 2.50.75 4007PCE 1.5 1.5 2.5 1.5 2.51.5 4015PCE 1.5 1.5 2.5 1.5 2.52.2 4022PCE 1.5 1.5 2.5 1.5 2.54.0 4037PCE 1.5 1.5 2.5 1.5 2.55.5 4055PCE 1.5 2.5 2.5 1.5 2.57.5 4075PCE 2.5 4 2.5 1.5 2.511 4110PCE 4 6 4 1.5 415 4150PCE 6 10 6 2.5 1018.5 4185PCE 10 10 10 2.5 1022 4220PCE 16 16 10 4 1630 4300PCE 25 25 16 6 1637 4370PCE 25 35 25 10 1645 4450PCE 35 35 35 35 1655 4550PCE 50 50 50 35 2575 4750PCE 95 95 70 35 50VoltageclassApplicablemotor (kW) Inverter type-formWire size (mm2 )Power circuitDC wireBrakingresistor(Optional)Ground-ing wireInput Output3-phase480 V0.75 VFAS3- 4004PCE 1.5 1.5 2.5 1.5 2.51.5 4007PCE 1.5 1.5 2.5 1.5 2.52.2 4015PCE 1.5 1.5 2.5 1.5 2.54.0 4022PCE 1.5 1.5 2.5 1.5 2.55.5 4037PCE 1.5 2.5 2.5 1.5 2.57.5 4055PCE 2.5 4 2.5 1.5 2.511 4075PCE 4 6 4 1.5 415 4110PCE 6 10 6 2.5 1018.5 4150PCE 10 10 10 2.5 1022 4185PCE 10 16 10 4 1630 4220PCE 16 25 16 6 1637 4300PCE 25 35 25 10 1645 4370PCE 35 35 35 16 1655 4450PCE 50 50 50 35 2575 4550PCE 70 95 70 35 5090 4750PCE 95 120 95 35 70Memo • The wire size of this chapter comply with IEC60364-5-52 (Grounding wire: IEC60364-5-54). Itdoes not comply with UL Standard.• For the wire size to comply with UL Standard, refer to [3. 2. 3].