Appendix1. System Specification Of OIS-DS/SVR-DS46Appendix Table1.1 System Specification of OIS-DS/SVR-DS(2)Item Specifications RemarksRemote Operation Analog : 3 step increment/decrement for SV and MVDigital : 2 action operation from tag display patternsDedicated keys (optional)Operable with the mouse(touch panel) on thewindow if there is nodedicated keyAlarm ConfirmationMethodProcess Alarm: Selected from A/B/C Type Cs (for each tag)System Alarm: Type BUnconfirmed alarmsblinks.Alarm Grade 3 levels (Major, Medium, Minor), Warning, NoneAlarm Grade Pattern None Any grade may bespecified.Alarm Monitor ON/OFF Process alarm: for each tagfor each tag-specific alarmSystem alarm: for each stationfor each card or deviceSignal Category 64 signal categories/systemTagging Directly registered to tagsService NameTag Number CharacterTag NameSignal Category NameIndicator NameStation NameIndustrial UnitTagging CharacterGuidance NameTrend Group NameANK 16 charactersANK 32 charactersANK 16 charactersANK 16 charactersANK 32 charactersANK 16 charactersANK 16 charactersANK 40 charactersANK 30 charactersTag Grouping 4, 8 or 16 tags/group2560 groups/systemTag Display Pattern One display size Customization andzooming of windows arepossible.Historical Database SVR filingNo. of Registered Items 5000 items/system Can be made redundant.Record Cycle 5 seconds to 1 day, 15 types and 200 tags/second (on HDD)No. of Saved Samples Max. 10000 items (on HDD)/tagMax. 20000000 items/systemUsed in Historical Trendand Report Function.Trend Screen 8 pens/groupMax. 1024 screens/systemSaved data can bedisplayed on multipleSVRís.