23MMW-AP___1CHQE18-361Characteristics of Hot Water Module flow rate and pressure lossThe following graph shows the range of flow rates used for the Hot Water Module, and the characteristic pressurelosses. Use this as an aid in the local pump procurement process.048 type Min. Rated Max.Water flow rate (L/min) 34 40 46Pressure loss (kPa) 12 15 18.50510152025303530 40 50Flow rate (Rating): 40 L/minAvailable flow range34 to 46 L/minPressure loss (kPa)Flow rate (L/min)