11.8"42.4"Left Side View30.1"Front ViewTITLEDRAWING NO. REV.NOTESA B C D E F G H I J1234567891012345678910150kVA G8000 Series UPS3-Breaker Maintenance Bypass PanelMBSB80-225-43 1.052C52M52LMaintenanceBypass Breaker225 Amp M.L.O.w/ (1) #6-250kcmilLug per Phase (typ)Front View(Door Removed)27.0"39.3"Utility FeedUPS BypassInput BreakerUPS OutputBreaker225 Amp Box-Mounted Neutral w/(2) #6-250kcmil Lugs0.5" Dia.Mounting Hole (4)To Critical LoadA B CNPart No. UPSKVABreakerType Voltage kAIC rating at480/600VUPS OutputAmp Rating150MBSB80-225-43 FD 480/600 25/14180EnclosureBox/TrimFinishBreakersWeight- NEMA 1, Surface-Mount (UL Listed).- 12-Gauge painted steel, trim held with adjustable clamps; Door equipedwith one 3x5 directory cardholder and Corbin type 15767 Snaplock.- Beige polyester powdercoat on all surfaces, treated with sealer.- Cutler-Hammer thermal-magnetic type, 225A frame, 3-pole, trip settings asshown, supplied with (1) #4-4/0 terminal lug per phase.- Approximately 190 lbs total.Feed From UtilityFeed To Critical Load52C225AT52M225AT52L225ATSTA B CABCABCA B CFeedfromUPSOutputFeed toUPSInputN1) This drawing is for illustration purposes only and is subject to change without notice. TICis not responsible for any errors or omissions.TOSHIBAINTERNATIONAL CORPORATIONHouston Texas, USATHIS MATERIAL IS THE EXCLUSIVE PROPERTY OFTOSHIBA INTERNATIONAL CORPORATION AND SHALL NOTBE REPRODUCED, USED, OR DISCLOSED TO OTHERSUNLESS PRIOR WRITTEN AUTHORIZATION IS OBTAINED.Drawn byEODate 07/07/04Approved byJISDate 07/07/04