14400 Series UPS Seismic Kit Installation Instructions – 94016-0024400 Series UPS Seismic Adapter KitInstallation InstructionsDate: March 2020Doc. No.: 94016-002The 4400 Series cabinets can be installed to meet California OSHPD seismic specifications using theoptional Seismic Kit and the floor anchorages specified below.These instructions describe how to install the seismic adapter kits on the 4400 Series UPS, Battery , andAuxiliary Cabinets. There is a SEISMIC KIT for each cabinet style: 15-30 kVA, 50 kVA, and 80 kVA.1. 4400 15-30kVA Seismic Installation2. 4400 50kVA Seismic Installation3. 4400 80kVA Seismic Installation1 4400 15-30kVA Seismic InstallationTable 1 lists the contents of the 4400 15-30kVA Seismic Kit. Figure 1.1 shows the order of assembly forthe [bolt + lockwasher + washer] fastener group.TABLE 1 15-30KVA SEISMIC CONTENTS440300SEISMICKIT ContentsNo. P/N* Description Quan1 93437 TOP SEISMIC BRACKET 30kVA) 13 67813 BASE MOUNTING BRACKET, 14-a – Hex Bolt, 1/4—20,1-1/2” 14-b – Flat Washer, 1/4 14-c – E—Ring, F/0.25 Shaft 111-a – Hex Bolt, 5/16—18 x 1” 1011-b – Lock Washer, 5/16 1011-c – Flat Washer, 5/16 10– 94016 4400 Seismic Kit InstallationManual1abcFIgUrE 1.1: FASTENErgrOUP (BOLT +LOCK WASH-Er + WASHEr) Cabinet Footprint1.75 in(44.4 mm)2.75 in(70 mm)2.0 in(51 mm)Conduit Knock-out(3 Places)34.05 in.(865 mm)12 in (305 mm) 12 in (305 mm)9.22 in (234 mm)4.28 in(109 mm)5.55 in(141 mm)Base Plate Footprint1/2 in. Bolt (6)FIgUrE 1.2: 15-30KVA SEISMICANCHOrAgE - FLOOr PATTErN