GENERAL DESCRIPTIONPage 8SERVICE CONDITIONSApplication ConditionThe type HCV vacuum contactor is manufactured in accordance with IEC 60470 (1974), NEMA ICS 3 Part 2(1993). The vacuum contactor should be used in the following conditions.Table 1Normal Service ConditionsLess than 2,000 m(6600 ft)Above 2,000 m consult factory-5“C min. to +40°C max.Its average over a period of24 hr does not exceed +35°C.45% min. to 85% max.20 Hz - 1G or less30G43 lbs.Latched type 44 lbs.- Altitude:-Ambient temperature:-Relative humidity:-Vibration:-Shock-WeightIf the contactor is to be used in conditions other than those specified above, piease consult ToshibaInternational Corporation.Table 2General Aoplication and Load Data3 Phase Capacitor1.OFF Syn Motor 3 PhaseTransformerSystemVoltage0.8PF Ind/SynMotor1500kVAR2000kVAR2000kVAR2000kVAR2000HP2500HP3500HP5000HP1500kVA2000kVA3000kVA4000kVA2.2-2.5kV3.0-3.3kV4.0-5.OkV6.0-6.6kV '1750HP2250HP3000HP4500HPThe above table is based on general load data and standard application. Lower limitations may apply onspecific applications (i.e. applications above 6600 feet elevations) .Location conditionThe location where the contactor is to be installed should be free from dust, corrosive gas and moisture.When it is to be used in a chemical plant or in outdoor applications, take necessary precautions againstcorrosion, water seepage and condensation.