6F2S1915 (0.46)GRZ200 (Soft 031 & 032)- 790 -TPOS01 function (Function ID: 513001)“TPOS01_P3SL_BO_FLG”(513001 8A04011DC8)DEV01_CONTROL_REQCommand “P3-Control” from the remoteILK† condition (“P3”) passedEither “SBO mode” or “DIR mode”(e.g., “ctlmodel” in IEC61850*)In SBO operateIn DIR operateSelect “Failed”513001 7004016D08TPOS1-P3To BO connectionInput OutputSelection logic in TPOS010.1s0 t0.6s0 t&&&&&Select “success”“Automatic sequence control function (AQEQ)§” in progressASEQ_MULTI_SELSelect condition‡1≥Select commandwith ILK† conditionOperate commandwith ILK† conditionSelect commandwithout ILK† conditionOperate commandwithout ILK† conditionFor SBO operationFor DIR operationTo “Wait for a command”For DIR operationFor SBO operationFigure 4.9-7 Select ‘P3-control’ from the remote-end in TPOS01†††Note:The ILK function provides the operation criteria for “P3 control”.††Note: To identify the input and output points of the other TPOS logics, see Table 4.9-5,Table 4.9-7 and Table 4.9-10.§Note:An automatic sequence control (ASEQ) function can provide sequential signals forautomatic control. The TPOS01 operation is blocked for the ASEQ function whenit is in operation. For more information regarding the ASEQ function, see ChapterControl and monitoring application: Automatic sequence control function.Output signal to BOThe TPOS01 function, in Figure 4.9-7, can issue a signal “Select success” at the output point“TPOS01_P3SL_BO_FL” when the TPOS01 function determines that the received signal“Select command P3 (Remote-P3-Control)” is true. If the TPOS01 function determines that the“Remote-P3-Control” is not true, the TPOS01 function returns to the “Wait for a command”stage.