ACE-tronics G9 ASD Installation and Operation Manual 187AM Output Terminal AdjustmentProgram Terminal Analog Output TerminalsThis parameter is used to calibrate the AM analog output.To calibrate the AM analog output connect a voltmeter to the AM and CCterminals.With the ASD is running at a known value (e.g., output frequency), adjust thisparameter until the associated function of parameter F670 produces the desiredDC level output at the AM output terminal.See F670 for additional information on this setting.Direct Access Number — F671Parameter Type — NumericalFactory Default — 512Changeable During Run — YesMinimum — 1Maximum — 1280MON1 Terminal Meter SelectionProgram Terminal Analog Output TerminalsThis parameter is used to set the output function of the MON1 analog outputterminal. The available assignments for this output terminal are listed in Table 8on pg. 240.The MON1 analog output terminal produces an output voltage or current that isproportional to the magnitude of the function assigned to this terminal.Note: The Expansion IO Card Option 2 option board (P/N ETB004Z)is required to use this terminal.See the Expansion IO Card Option 2 Instruction Manual (P/N 58686) foradditional information on the function of this terminal.MON1 Terminal Setup ParametersF672 — MON1 Output FunctionF673 — MON1 Terminal Meter AdjustmentF688 — MON1 Voltage/Current Output SwitchingF689 — MON1 Output Gradient CharacteristicF690 — MON1 Bias Adjustment Set Zero LevelDirect Access Number — F672Parameter Type — Selection ListFactory Default — Output VoltageChangeable During Run — YesMON1 Terminal Meter AdjustmentProgram Terminal Analog Output TerminalsThis parameter is used to set the gain of the MON1 output terminal and is usedin conjunction with the settings of parameter F672.See parameter F672 for additional information on this setting.Direct Access Number — F673Parameter Type — NumericalFactory Default — 512Changeable During Run — YesMinimum — 1Maximum — 1280F671 F673Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com