TOSHIBA114.0 Connection Instructions and Diagrams 14 & 18kVA4.1 Battery ConnectionsThe following illustrations details the wiring connections between the UPS and theBattery Unit.DANGERContacts are not rated with interrupting capacity. DO NOT attempt to connect theUPS to the Battery Cabinet without having the MCCB switch on the rear panel of theBattery Unit, in the OFF position.4.2 14kVA/18kVA illustrationThe following diagram shows the rear view of a 14kVA / 18kVA UPS and 18kVABattery Cabinet. NOTE: Use only compatible cabinets! Refer to page 8.4.3 Connection Procedure1) Ensure all power is locked and tagged out.2) Remove the Battery Connector cover mounted on the top of the UPS back panel.3) Plug the DC Connectors of the Battery unit into the DC Connector socket on theUPS unit (see power connections section 3.1).4.4 Charger ConnectionBattery Cabinet model UE31-BC-1825 requires 240V connection between the UPS andBattery Cabinet for battery charging. This connection is made from CN14A of theBattery Cabinet to CN14 of the UPS (and CN14A of battery cabinet 2 to CN24 ofbattery cabinet 1 if paralleling cabinets). NOTE: Without this connection the batterycabinet will not be able to charge its batteries, thus preventing extended backuptime during a power outage.1600EP14/18kVA UPS 8-18kVA Battery Cabinet