Toshiba International CorporationUninterruptible Power SystemsUE3G2L036C61TMBProduct SpecificationsINPUT Voltage 240VacVoltage Range 168V~264V (+10% to -30%)Frequency 50/60 Hz Auto SensingSynchronization window ± 3HzPower Factor Greater than 0.95THD Current Less than 5% at Full LoadTopology True On-Line, Double Conversion, Input PF CorrectionOUTPUT Voltage 240VacCapacity (VA) 3600Capacity (W) 3100Voltage Regulation ± 3%Voltage Distortion Less than 6% THD at Full Non-Linear Load. Less than 3% THD at full Linear Load.Step Load ± 8 % max from 100% to 0 % or from 0% to 100 % linear loadRated Current 15AMax Peak Current 45A1600EP Series 3.6kVA 240V In - 240V Out Tower Maintenance Bypass SolutionToshiba's 1600EP Series is an on-line Uninterruptible Power Supply (UPS) systemsprovide continuous computer-grade ac power in a compact, high performance, and energyefficient unit. The UPS unit assures safe and reliable operation of critical office equipment.This can range from word processors and personal computers to mini-computers and localarea networks. All units feature an audible alarm, which sounds if the battery voltage dropsbelow standard during use. This is an additional aid to help in retaining the valuable officedata banks. All units allow for computer interfacing.This model is a Maintenance Bypass solution. Maintenance Bypass solution is a twobreaker maintenance bypass panel. This is a 240V input and 240-output solution.