Operation11.3 Effects on changing the potentiometer settingsSIRIUS 3RW30 / 3RW4084 Manual, 10/2018, NEB535199502000/RS-AB/00511.3 Effects on changing the potentiometer settingsPotentiometer Change Reaction / behaviorStartupReaction / behaviorBypass operationReaction / behaviorRun-downStarting voltage Increase voltage Effective at next start Effective at next start Effective at next startRamp-up time Extend time Change effective im-mediatelyEffective at next start Change effective im-mediatelyCurrent limiting In case of limitingfactorChange effective im-mediatelyEffective at next start Change effective im-mediatelyRamp-down time Extend time Effective at next start Effective at next shut-downChange effective im-mediately in downrampCLASS setting Change from 10 to 20 Change effective im-mediatelyChange effective im-mediatelyChange effective im-mediatelyMotor current setting Change Change effective im-mediatelyChange effective im-mediatelyChange effective im-mediately