Configuring with Studio 5000 Logix Designer3.3 Creating a Studio 5000 Logix Designer projectIdent profile, Add-on instruction for Rockwell systems12 Function Manual, 01/2019, C79000-G8976-C410-033.3 Creating a Studio 5000 Logix Designer projectThe modules can be integrated into Rockwell automation systems using Studio 5000 LogixDesigner. The connection is via Ethernet/IP. Following this, you can configure the RF68xRreader using WBM while you control the work with the module using the add-on instructionsof Studio 5000 Logix Designer.RequirementThe module is connected, has started up and an IP address has been assigned to thedevice. The Studio 5000 Logix Designer was started.ProcedureFollow the steps below to create a new project:1. Start the Studio 5000 Logix Designer.2. Create a new project.Select the controller you are using and configure the project properties.3. Change to the Project view.4. Right-click on "Ethernet" in the "Controller Organizer > I/O Configuration" area.5. In the shortcut menu, select the menu command "New Module...".The input screen "Select Module Type" is opened.6. Select the module (e.g. "RF68xR") and click on the "Create" button.The input screen "New Module" opens.7. Enter the name of the device in the "Name" text box.8. Enter the IP address of the device in the "IP address" text box.9. Click the "Change" button.The input screen "Module Definition" opens.10.In the "Size" box change the data word size from "SINT" to "INT".11.Confirm your entry with "OK".12.Confirm with "OK".