5 MICROMASTER 440 specifications Issue 10/03MICROMASTER 440 Operating Instructions198 6SE6400-5AW00-0BP0Input voltage range 3 AC 380 V – 480 V, ± 10 %(Unfiltered)Order No. 6SE6440- 2UD13-7AA12UD15-5AA12UD17-5AA12UD21-1AA12UD21-5AA12UD22-2BA12UD23-0BA12UD24-0BA12UD25-5CA12UD27-5CA1[kW] 0.37 0.55 0.75 1.1 1.5 2.2 3.0 4.0 5.5 7.5Output Rating (CT) [hp] 0.5 0.75 1.0 1.5 2.0 3.0 4.0 5.0 7.5 10.0Output Power [kVA] 0.9 1.2 1.6 2.3 3.0 4.5 5.9 7.8 10.1 14.0CT Input Current 1) [A] 1.5 1.9 2.4 3.7 4.8 6.5 8.6 11.6 15.6 22.0CT Output Current [A] 1.3 1.7 2.2 3.1 4.1 5.9 7.7 10.2 13.2 19.0VT Input Current 1) [A] - - - - - - - - 16.0 22.5VT-Output Current [A] - - - - - - - - 19.0 26.0Fuse [A] 10 10 10 10 10 16 16 20 20 32Recommended 3NA 3803 3803 3803 3803 3803 3805 3805 3807 3807 3812for UL specified * * * * * * * * * *[mm 2] 1.0 1.0 1.0 1.0 1.0 1.5 1.5 2.5 2.5 4.0Input Cable Min. [awg] 17 17 17 17 17 15 15 13 13 11[mm 2] 2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0 10.0Input Cable Max. [awg] 13 13 13 13 13 9 9 9 7 7[mm 2] 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 2.5 4.0Output Cable Min. [awg] 17 17 17 17 17 17 17 17 13 11[mm 2] 2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0 10.0Output Cable Max. [awg] 13 13 13 13 13 9 9 9 7 7[kg] 1.3 1.3 1.3 1.3 1.3 3.3 3.3 3.3 5.5 5.5Weight [lbs] 2.9 2.9 2.9 2.9 2.9 7.3 7.3 7.3 12.1 12.1Order No. 6SE6440- 2UD31-1CA12UD31-5DA12UD31-8DA12UD32-2DA12UD33-0EA12UD33-7EA12UD34-5FA12UD35-5FA12UD37-5FA1[kW] 11.0 15.0 18.5 22.0 30.0 37.0 45.0 55.0 75.0Output Rating (CT) [hp] 15.0 20.0 25.0 30.0 40.0 50.0 60.0 75.0 100.0Output Power [kVA] 19.8 24.4 29.0 34.3 47.3 57.2 68.6 83.8 110.5CT Input Current 1) [A] 32.3 38.5 47.1 56.3 78 95 122 148 188CT Output Current [A] 26.0 32.0 38.0 45.0 62.0 75.0 90.0 110.0 145.0VT Input Current 1) [A] 30.5 37.2 43.3 59.3 71.7 86.6 103.6 138.5 168.5VT-Output Current [A] 32.0 38.0 45.0 62.0 75.0 90.0 110.0 145.0 178.0Fuse [A] 35 50 63 80 100 125 160 200 250Recommended 3NA 3814 3820 3822 3824 3830 3832 8036 3140 3144for UL specified 3NE * 1817-0 1818-0 1820-0 1021-0 1022-0 1224-0 1225-0 1227-0[mm 2] 6.0 10.0 10.0 16.0 25.0 25.0 35.0 70.0 95.0Input Cable Min. [awg] 9 7 7 5 3 3 2 -2 -3[mm 2] 10.0 35.0 35.0 35.0 35.0 35.0 150.0 150.0 150.0Input Cable Max. [awg] 7 2 2 2 2 2 -5 -5 -5[mm 2] 6.0 10.0 10.0 16.0 25.0 25.0 35.0 70.0 95.0Output Cable Min. [awg] 9 7 7 5 3 3 2 -2 -3[mm 2] 10.0 35.0 35.0 35.0 35.0 35.0 150.0 150.0 150.0Output Cable Max. [awg] 7 2 2 2 2 2 -5 -5 -5[kg] 5.5 16.0 16.0 16.0 20.0 20.0 56.0 56.0 56.0Weight [lbs] 12.1 35.0 35.0 35.0 44.0 44.0 123.0 123.0 123.01) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the linesupply V k = 1 % referred to the rated drive converter power and a rated line supply voltageof 400 V without line commutating reactor. If a line commutating reactor is used, the specifiedvalues are reduced by between 70 % and 80 %.* UL listed fuses such as Class NON from Bussmann are required for use in America* UL listed fuses such as Class NON from Bussmann are required for use in America