231/327Building Technologies Basic Documentation LMV5... CC1P7550en15 Technical data 22.05.2018Total load on contactsMains voltage AC 120 V-15% / +10%AC 230 V-15% / +10%∂ Input current of unit (safety loop)total load on contacts resulting from:- Fan motor conductor- Ignition transformer- Valve- Oil pump / magnetic clutchMax. 5 A Max. 5 ASingle contact loadFan motor contactor (rated voltage)∂ Rated current 1 A 1 A∂ Power factor Cos ι >0.4 Cos ι >0.4Alarm output (rated voltage)∂ Rated current 1 A 1 A∂ Power factor Cos ι >0.4 Cos ι >0.4Ignition transformer (rated voltage)∂ Rated current 1.6 A 2 A∂ Power factor Cos ι >0.2 Cos ι >0.2Gas valves (rated voltage)∂ Rated current 1.6 A 2 A∂ Power factor Cos ι >0.4 Cos ι >0.4Oil valves (rated voltage)∂ Rated current 1.6 A 1 A∂ Power factor Cos ι >0.4 Cos ι >0.4Cable lengths∂ Main cable Max. 100 m(100 pF/m)Max. 100 m(100 pF/m)∂ CFN cable Max. 100 m(100 pF/m) ¹)Max. 100 m(100 pF/m) ¹)∂ Analog cable Max. 100 m(100 pF/m)Max. 100 m(100 pF/m)∂ Flame detector Refer to chapter Technical Data / Flamesupervision∂ CAN-bus Total length max. 100 mΒ Note!¹) If the cable length exceeds 50 m, no additional loads may be connected to thestatus inputs, refer to Power supply for LMV5!If a certain cable length is exceeded, the actuators must be powered by a transformerlocated near the actuators.Loads on outputterminals