7Building Technologies A6V10229545_g_en_--Fire Safety 2018-06-15Technical dataFDS229-R FDS229-AOperating voltage DC 12…33 VOperating currentჀ StandbyჀ Sound activatedჀ Additional optical indicator activatedჀ Sound and indication activated250 ˩A3.5 mA3.5 mA7.0 mASounds 112 activation levels3 sound levelsSound level 80…99 dB(A)Number of beacon patterns 1 (intermittent)Light intensity at DC 32 V,depending on viewing angle -30°…+30°1.27…3.2 cd 1.1…2.8 cdExternal alarm indicator 2Operating temperature -25…+65 °C -25…+55 °CStorage temperature -30…+75 °CAir humidityื 95 % rel.Communication protocol FDnet/C-NETConnection terminals According to detector baseColor Transparent red Transparent orangeEN 60529/IEC 60529 protection category: FDS229 withჀ Base FDB221 or FDB222Ⴠ Base attachment FDB291Ⴠ Base FDB221 and sealing element FDBZ295Ⴠ Base attachment humid FDB293Wall mounting with feed lineFrom below IP43, otherwise IP42IP44IP54Standards EN 54-3, EN 54-17ApprovalsჀ VdSჀ LPCBჀ DNV GL (marine)G207156531p/03MEDB00003UVG207156531p/02MEDB00003UVC-NET, FDnet system compatibility FS720, FS20, FC360Siemens Schweiz AG; Theilerstrasse 1aCH-6300 ZugTechnical data: see doc. 01009507FDS229 - Sounder incl. short-circuit isolator for use in fire detection and fire alarm systems installed in buildings.305/2011/EU (CPR): EN 54-3 / EN 54-17 ; 2014/30/EU (EMC): EN 50130-4 / EN 61000-6-3 ; 2011/65/EU (RoHS): EN 50581The declared performance and conformity can be seen in the Declaration of Performance (DoP) and the EU Declaration of Conformity (DoC), which isobtainable via the Customer Support Center: Tel. +49 89 9221-8000 or https://siemens.com/bt/downloadDoP No.: 0786-CPR-20345; DoC No.: CED-FDS2290786 FDS229-A / FDS229-R