8svt
vtS7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31xA5E00105492-03 5-49Xh
vtDisturbance of data traffic might occur on the bus.A bus segment must always be terminated at both ends with the terminatingresistor. This, for example, is not the case if the last slave with bus connector is offpower.Since the bus connector draws its power from the station, the terminating resistorhas no effect.Please make sure that power is always supplied to stations on which theterminating resistor is active.As an alternative, you can also use the PROFIBUS Terminator as active bustermination.