Info Alert DescriptionThis alert appears when the relay is powered on in the battery mode.This alert appears when the relay goes into sleep mode.This alert appears when there is insufficient energy to perform thefollowing actions:• Turn on backlight• To operate or reset the binary outputsThis alert appears when you select to clear the fault records withoutacknowledging the latest fault by resetting the flag.This alert appears when the relay is powered with phase CT.This alert appears when the relay is powered with auxiliary powersupply.Parameter Edit Screen7SR45 Argus Relay allows you to edit the parameter value in the LCD.To edit any parameter, follow the procedure:² From the Relay Identifier screen, navigate to the Parameter screen.² In the Parameter screen, press ENTER key to display the edit screen.² In the Edit screen, you can edit the parameter value in the editable field.² Press ▲ key and ▼ key to select the valid value.² Press ENTER to save the parameter value.To discard the parameter value, press the CANCEL key.² Press CANCEL until the Save and Restart pop-up screen is displayed.² Press ENTER to save the configuration in memory.4.6.4Using the Relay Fascia4.6 Notification AlertsReyrolle, Operating, Manual 57C53000-B7040-C101-1, Edition 08.2020