3. Installing the Product Confidential124 English 8/2019. Rev 0.0Figure 3-152: System BMS Install Setting WindowImportant Change the values according to your system configuration. [Count] Rack per 1 System: Number of racks connected to the same System BMS [Count] Module per 1 Rack: Number of modules for each rack (e.g., 136S1P Rack has 17modules) [TCPIP] items (IP Address, Subnet Mask, Gateway, Port)TCP/IP address and port (17.91.30.246/502 by default), subnet mask (255.255.224.0 by default)and gateway (17.91.1.2 by default) should be changed according to your network environment.Set the port number to the factory default values(Port#01: 502, Port#02: 602, Port#03: 702) [RTU] items: set to the factory default values.(Baud rate: 0, Parity: 1, Slave ID: 0x27) [Operation] Neutral Control EnableSet to “0” if all racks are connected in parallel (default).Set to “1” if the two racks are connected in series for a three-wire connection. [Operation] Customer IDSet according to the dry contact input and output options. Refer to 2.1.3 SMPS Assembly (TypeA / Type B)