Page 4245349C © 2001 RadionicsD6412 Installation GuideD6412Off-Board Outputs10.2.5 D9529 to D6412 SDI Bus Wiring ConnectionsRefer to Table 11 for the SDI bus wiring length requirements.If the D9529 is to be installed far from the control panel, then the control panel cannot be used to power theD9529. An external power supply must be used. See Figure 27 for external power supply connections.Power Source #22 AWG (0.8 mm) #18 AWG (0.8 mm)D6412 to D9529 D6412 40 ft. (12.2 m) 80 ft. (24.4 m)D6412 to D9529 External PowerSupply1000 ft. (305 m) 2000 ft. (610 m)External Power Supply to D9529 40 ft. (12.2 m) 80 ft. (24.4 m)Table 11: D9529 Wire LengthsPower down the panel to connect the D9529 as shown in Figure 26.YGBRNC NOC8YBRGYellowYellowGreenGreenBlackBlackRedD9529D6412RedOutput Activated StateNC NOCOutput De-activated StateNC NOCFigure 26: Wiring the D9529 to the D6412