Page 4045349C © 2001 RadionicsD6412 Installation GuideD6412Off-Board Outputs10.0 Off-Board Outputs10.1 OverviewYou can expand the total number of D6412 programmable outputs to 20 using the D9529 Octo-Output Module(two required for 20 outputs) or X7410i Module. Instructions for the D9529 Module are included in this manual (aswell as with the module). The X7410i Module emulates two D9529 Modules. X7410i specific instructions areincluded with the module.10.2 D9529 Octo-Output Module10.2.1 OverviewThe D9529 Octo-Output Module allows you to add outputs to your system in groups of eight. You can add up to twoD9529 Octo-Output Modules to the D6412. Combining the four on-board programmable outputs with two D9529Octo-Output Modules makes a total of 20 programmable outputs available. Review Section 5.0, Power Outputs,to be sure you provide enough power for the Octo-Output Modules and any other powered devices you connect tothe panel.You can assign any of the programmable output functions to the Octo-Output Module’s individual outputs separately.See Outputs in the D6412 Program Entry Guide (P/N: 45351) for programming details.D9529 restricted from fire systems: The D9529 relay outputs are not supervised and cannot be used in fire orcombined fire/burglary installations for primary indicating devices.Current Draw: 10 mA Standby plus 40 mA for each energized output (relay) for a total of 330 mA maximum withall eight outputs energized.Refer to the D9529 Installation Guide (P/N: 46925) for complete installation, addressing and operating instructions.10.2.2 Configuring the D9529 Octo-Output ModuleWARNINGOutputs may activate when setting the D9529’s switches, programming the panel, resetting the panel orapplying power to the panel . You may wish to disconnect equipment connected to outputs while performingthese functions.10.2.3 Relay OutputsEach D9529 output provides a Form C dry contact rated for 5.0 A at 28 VDC. Normally-open, common, andnormally-closed terminals are available for each relay output. When an individual output is activated, there iscontinuity between the normally-open and common terminals. When the output is not activated, there is continuitybetween the normally-closed and common terminals.