PAGE 34 SMED SEMI VERTICAL - HUSSMANNISSUE POSSIBLE REASON REMEDIAL ACTIONProduct temperature ishigher than requirementStore condition is warmer or more humidthan climate class 3 (25°C/60%RH)Check store climate control is operatingcorrectly.Refrigeration plant is not running oroperating at inappropriate settings orconditionsCheck for refrigeration plant operation.If refrigeration is running and otherpossible reasons are eliminated thencall refrigeration mechanic to checkplant operation.Evaporator pressure is not set correctly Check suction pressure settings at thecase and if required adjust as per casespecificationInsufficient or no air flow appears at thecase air curtain.Check if evaporator coil is iced. If ice ispresent then check defrost settings asper the manufacturers guideline or setto suite the store operating condition. Acolder store may require longer defrostduration. A humid store may needmore frequent defrost.Check if case fans are turned on oroperating correctly. If any doubt of fanoperation contact technician.Case shelf arrangement has been deviatedsignificantly from original specified setupRe-do the shelf arrangement as perthe original specificationAir Return is blocked by merchandise Move merchandise to be within theload limit.None of above Contact your refrigeration serviceprovider.6.1 TROUBLESHOOT TABLETROUBLESHOOTING |