11DAILY USER´S MANUAL • EBL128 VERSION 2.2.X • DOCUMENT NUMBER: MEW01786 • REVISION: 1ContinuedB6 Re-enable zone-address Select an alarm point (zone-address).To re-enable the selected alarm point press "A".B7 Re-enable outputOnly disabled types will be shown.Use the keypad to select type ofoutput:- 0 = Loop unit output.- 1 = C.i.e. output S0 or S1.- 2 = C.i.e. output R0.- 3 = C.i.e. expansion board output.Press "A".Select the output to re-enable. Press "A".B8Re-enable all control,ventilation, exting orinterlocking outputsOnly disabled types will be shown.Use the keypad to select type ofoutput:- 0 = Outputs type Control.- 1 = Outputs type Ventilation.- 2 = Outputs type Extinguishing.- 3 = Output type Interlocking.Press "A".B9 Disable / re-enable alarmdevicesSelect “Alarm devices in normal condition” or “Alarm devicesdisabled”.Press "A". The status is changed.B10 Disable / re-enable outputsfor routing equipmentThe actual status for the output FIRE and FAULT respectively will beshown. Use the keypad to select:- 1 = enabled or- 0 = disabled for the output respectively.Step right / left with the arrow keys.Press "A". The status is changed.B11 Disable / re-enable alertannunciation function“Alert annunciation function is in normal operation” or “Alertannunciation function turned off” will be shown.Press "A". The status is changed.The AA function will stay disabled until re-enabled again via thismenu.NOTE! Disabled Alert Annunciation function is indicated by LED"Fault / Disablements Fire brigade tx delay" turned off.