Table 11. Electrical outputAll models Normal mode Battery modeVoltage regulation ±1% ±1%Efficiency > 98% (High Efficiency mode)> 94.5% for 8-11kVA models> 91%Frequency regulation Sync with line ±5% of nominal line frequency(outside this range: ±0.5% of auto-selectednominal frequency)±0.5% of auto-selected nominalfrequencyFrequency 50 or 60Hz, autosensing or configurable as a frequency converterOutput overload 100-102% : no alarm102-110% : load transfers to Bypass mode after 2 minutes110-125% : load transfers to Bypass mode after 1 minute125-150% : load transfers to Bypass mode after 10s> 150% : load transfers to Bypass mode after 900msOutput overload(Bypass mode)100-125% : no alarm125-150% : UPS shuts down after 1 minute> 150% : UPS shuts down after 1sVoltage waveform SinewaveHarmonic distortion < 2% THDV on linear load< 5% THDV on non-linear loadTransfer time Online mode: 0 ms (no break)High Efficiency mode: 10ms maximum (due to loss of utility power)Power factor 0.9Load crest ratio 3 to 1Table 12. Electrical output connectionsModel Output connection Output cable5594-8PX, 5594-8KX5594-9PX, 5594-9KX(4) C19 via MBP Not providedTable 13. AC input and output (1Phase models)5594-8KX 5594-9KXAC Input power 200-240VAC, 50/60Hz, 1ph, 40A max 200-240VAC, 50/60Hz, 1ph, 50A maxAC Output power 50/60Hz, 1ph;200VAC, 8000VA, 7200W, 40.0A;208VAC, 8000VA, 7200W, 38.5A;220VAC, 8000VA, 7200W, 36.4A;50/60Hz, 1ph;200VAC, 10000VA, 9000W, 50.0A;208VAC, 10000VA, 9000W, 48.1A;220VAC, 11000VA, 9900W, 50.0A;64 6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's Guide