Installation and Commissioning ManualDocument Reference MTEC-HS-01 Rev 071 Author ADV-DC Page 303.3.8 OutputsThe “Cause and Effect” programming is a schedule of actions that will turn on one or more outputs dependant ona set of input events.The Outputs Option provides the means to create simple or complex “cause and effect” programming within thepanel. Delays can be introduced to allow a phased evacuation of a building (Note this is different to an“Investigation Delay” which is detailed in section 3.3.9) .This section describes the settings and options in detail for each parameter. Refer to Appendix 4 – Cause andEffect Programming Example for a description of how to program a typical requirement.More complex “Cause and Effect” programming may be undertaken using the PC Configuration tool.When the OUTPUTS Option is selected, the display shows the cause and effect programming for Output Group 1.For example:[Output Group 1] [ 3.9% Mem used]ZONE GROUP CAUSE STYLE=Delay->MODE1 1 ANY FIRE 00 - On2 1 ANY FIRE 00 - On3 1 ANY FIRE 00 - On4 1 ANY FIRE 00 - OnTo simplify the cause & effect programming, one or more outputs that will respond in the same way when thesame set of input events occurs can be grouped together. This association of outputs is called an Output Group.The panel can support up to 200 of these Output Groups.To select a different Output Group, highlight any group number and then enter the number of the output grouprequired using the number buttons. The display always shows the Output Group is shown in the top left corner.Press the ÏÐ buttons to scroll through the list of zones.Press theÍÎ buttons to select the fields for a particular zone.Press the 5 button to select a particular field option to change its setting.3.3.8.1 Default Output SettingsOn initial installation, or after clearing the configuration memory, all outputs are assigned to specific OutputGroups and will turn on immediately a single fire alarm occurs in any zone (any fault condition for the faultrelay). The default assignments are as follows:Output Device Output Group Cause and EffectOn-board Sounder A 1 Any fire in any zone – no delayOn-board Sounder B 2 Any fire in any zone – no delayOn-board Sounder C * 3 Any fire in any zone – no delayOn-board Sounder D* 4 Any fire in any zone – no delayOn-board Relay 1 200 Any fault in any zone – no delayOn-board Relay 2 199 Any fire in any zone – no delayOn-board Open Collectors 199 Any fire in any zone – no delayAll Loop Output Devices 199 Any fire in any zone – no delay* FCPTEC-HS-4400 only