Installation and Commissioning ManualDocument Reference MTEC-HS-01 Rev 071 Author ADV-DC Page 273.3.2.10 Detector TestingIndividual detectors can be tested to check the chamber response and illuminate the detector LED.While the address field is highlighted, press the ÏÐ buttons to scroll through the list of devices to the desireddetector (or key in the address, and then press the 5 button).A menu will appear to confirm that you want “Test This Detector”.Press the 5 button to confirm or press the ‘Esc’ button to cancel.Once selected, commands are sent to the detector to turn on the detector LED and put the chamber into test. The“Test” LED lights up and the panel display returns to the list of devices.After a few seconds the analogue signal will be seen to rise. If the detector is then left in the test condition, theDetector State will change to a “Fire Test” status.The test is cancelled as soon as the display is scrolled up or down or when the ‘View Devices’ option is exited.3.3.3 Loops - Auto Learn3.3.3.1 Normal Procedure / Initial learnThe panel can automatically learn the presence or absence of devices at all addresses connected to the loop. Whenthe Auto Learn option is selected, the panel starts searching each address on the loop to locate and find all of thedevices connected. A display is shown to indicate the progress of this procedure.For example:[Auto Learn Loop 1] HOCHIKIAddress 15 Devices found = 3When all addresses have been searched, the panel displays a summary screen showing the quantity of devicesfound for each type of device.For example:[Auto Learn Loop 1] HOCHIKIAddress 127 Devices found = 4OPT ION MUL TMP MCP SCC I/O ZMU OTHERS0 1 1 1 1 0 0 0 0This summary provides a quick check to ensure that the panel has found all of the devices that should beconnected to the loop.Press the ‘Esc’ button to return to the main Loops Menu.