E-4L90 Line Differential RelayGE Power ManagementE.2 DNP IMPLEMENTATION TABLE APPENDIX EEE.2 DNP IMPLEMENTATION TABLE E.2.1 IMPLEMENTATION TABLEThe following table identifies the variations, function codes, and qualifiers supported by the UR in both request messagesand in response messages. For static (non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07, or 08, will beresponded with qualifiers 00 or 01. Static object requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or28. For change-event objects, qualifiers 17 or 28 are always responded.Table E–2: IMPLEMENTATION TABLE (Sheet 1 of 4)OBJECT REQUEST RESPONSEOBJECTNO.VARIATIONNO.DESCRIPTION FUNCTIONCODES (DEC)QUALIFIERCODES (HEX)FUNCTIONCODES (DEC)QUALIFIERCODES (HEX)1 0 Binary Input (Variation 0 is used to requestdefault variation)1 (read)22 (assign class)00, 01 (start-stop)06 (no range, or all)07, 08 (limited qty)17, 28 (index)1 Binary Input 1 (read)22 (assign class)00, 01 (start-stop)06 (no range, or all)07, 08 (limited qty)17, 28 (index)129 (response) 00, 01 (start-stop)17, 28 (index)( see Note 2)2 Binary Input with Status(default – see Note 1)1 (read)22 (assign class)00, 01 (start-stop)06 (no range, or all)07, 08 (limited qty)17, 28 (index)129 (response) 00, 01 (start-stop)17, 28 (index)(see Note 2)2 0 Binary Input Change (Variation 0 is used torequest default variation)1 (read) 06 (no range, or all)07, 08 (limited qty)1 Binary Input Change without Time 1 (read) 06 (no range, or all)07, 08 (limited qty)129 (response)130 (unsol. resp.)17, 28 (index)2 Binary Input Change with Time(default – see Note 1)1 (read) 06 ( no range, or all)07, 08 (limited qty)129 (response130 (unsol. resp.)17, 28 (index)10 0 Binary Output Status (Variation 0 is used torequest default variation)1 (read) 00, 01 (start-stop)06 (no range, or all)07, 08 (limited qty)17, 28 (index)2 Binary Output Status(default – see Note 1)1 (read) 00, 01 (start-stop)06 (no range, or all)07, 08 (limited qty)17, 28 (index)129 (response) 00, 01 (start-stop)17, 28 (index)(see Note 2)12 1 Control Relay Output Block 3 (select)4 (operate)5 (direct op)6 ( dir. op, noack)00, 01 (start-stop)07, 08 (limited qty)17, 28 (index)129 (response) echo of request20 0 Binary Counter(Variation 0 is used to request defaultvariation)1 (read)7 (freeze)8 (freeze noack)9 (freeze clear)10 (frz. cl. noack)22 (assign class)00, 01 (start-stop)06 (no range, or all)07, 08 (limited qty)17, 28 (index)1 32-Bit Binary Counter(default – see Note 1)1 (read)7 (freeze)8 (freeze noack)9 (freeze clear)10 (frz. cl. noack)22 (assign class)00, 01 (start-stop)06 (no range, or all)07, 08 (limited qty)17, 28 (index)129 (response) 00, 01 (start-stop)17, 28 (index)(see Note 2)Note 1: A Default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. Type 30 (AnalogInput) data is limited to data that is actually possible to be used in the UR, based on the product order code. For example, SignalSource data from source numbers that cannot be used is not included. This optimizes the class 0 poll data size.Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respec-tively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change-event objects, qualifiers 17 or 28 are always responded.)Note 3: Cold restarts are implemented the same as warm restarts – the UR is not restarted, but the DNP process is restarted.