GE Multilin L30 Line Current Differential System 5-2095 SETTINGS 5.10 TESTING55.10.4 CHANNEL TESTSPATH: SETTINGS ÖØ TESTING ÖØ CHANNEL TESTSThis function performs checking of the communications established by both relays.Refer to the Commissioning chapter for a detailed description of using the channel tests.5.10.5 PHASOR MEASUREMENT UNIT TEST VALUESPATH: SETTINGS ÖØ TESTING ÖØ PMU TEST VALUES Ö PMU 1 TEST VALUES CHANNEL TESTS LOCAL LOOPBACKMESSAGE REMOTE LOOPBACK LOCAL LOOPBACKLOCAL LOOPBACKFUNCTION: NoRange: Yes, NoMESSAGE LOCAL LOOPBACKCHANNEL NUMBER: 1Range: 1, 2 REMOTE LOOPBACKREMOTE LOOPBACKFUNCTION: NoRange: Yes, NoMESSAGE REMOTE LOOPBACKCHANNEL NUMBER: 1Range: 1, 2 PMU 1 TEST VALUESPMU 1 TESTFUNCTION: DisabledRange: Enabled, DisabledMESSAGE PMU 1 VA TESTMAGNITUDE: 500.00 kVRange: 0.00 to 700.00 kV in steps of 0.01MESSAGE PMU 1 VA TESTANGLE: 0.00°Range: –180.00 to 180.00° in steps of 0.05MESSAGE PMU 1 VB TESTMAGNITUDE: 500.00 kVRange: 0.00 to 700.00 kV in steps of 0.01MESSAGE PMU 1 VB TESTANGLE: –120.00°Range: –180.00 to 180.00° in steps of 0.05MESSAGE PMU 1 VC TESTMAGNITUDE: 500.00 kVRange: 0.00 to 700.00 kV in steps of 0.01MESSAGE PMU 1 VC TESTANGLE: 120.00°Range: –180.00 to 180.00° in steps of 0.05MESSAGE PMU 1 VX TESTMAGNITUDE: 500.00 kVRange: 0.00 to 700.00 kV in steps of 0.01MESSAGE PMU 1 VX TESTANGLE: 0.00°Range: –180.00 to 180.00° in steps of 0.05MESSAGE PMU 1 IA TESTMAGNITUDE: 1.000 kARange: 0.000 to 9.999 kA in steps of 0.001MESSAGE PMU 1 IA TESTANGLE: –10.00°Range: –180.00 to 180.00° in steps of 0.05