5-210 L30 Line Current Differential System GE Multilin5.10 TESTING 5 SETTINGS5The relay must be in test mode to use the PMU test mode. That is, the TESTING Ö TEST MODE FUNCTION setting must be“Enabled” and the TESTING ÖØ TEST MODE INITIATE initiating signal must be “On”.During the PMU test mode, the physical channels (VA, VB, VC, VX, IA, IB, IC, and IG), frequency, and rate of change of fre-quency are substituted with user values, while the symmetrical components are calculated from the physical channels. Thetest values are not explicitly marked in the outgoing data frames. When required, it is recommended to use the user-pro-grammable digital channels to signal the C37.118 client that test values are being sent in place of the real measurements.MESSAGE PMU 1 IB TESTMAGNITUDE: 1.000 kARange: 0.000 to 9.999 kA in steps of 0.001MESSAGE PMU 1 IB TESTANGLE: –130.00°Range: –180.00 to 180.00° in steps of 0.05MESSAGE PMU 1 IC TESTMAGNITUDE: 1.000 kARange: 0.000 to 9.999 kA in steps of 0.001MESSAGE PMU 1 IC TESTANGLE: 110.00°Range: –180.00 to 180.00° in steps of 0.05MESSAGE PMU 1 IG TESTMAGNITUDE: 0.000 kARange: 0.000 to 9.999 kA in steps of 0.001MESSAGE PMU 1 IG TESTANGLE: 0.00°Range: –180.00 to 180.00° in steps of 0.05MESSAGE PMU 1 TESTFREQUENCY: 60.000 HzRange: 20.000 to 60.000 Hz in steps of 0.001MESSAGE PMU 1 TESTdf/dt: 0.000 Hz/sRange: –10.000 to 10.000 Hz/s in steps of 0.001