GE Multilin F60 Feeder Management Relay 6-196 ACTUAL VALUES 6.3 METERING66.3.7 FLEXELEMENTS™PATH: ACTUAL VALUES ÖØ METERING ÖØ FLEXELEMENTS Ö FLEXELEMENT 1(8)The operating signals for the FlexElements™ are displayed in pu values using the following definitions of the base units.6.3.8 TRANSDUCER I/OPATH: ACTUAL VALUES ÖØ METERING ÖØ TRANSDUCER I/O DCMA INPUTS Ö DCMA INPUT xxActual values for each dcmA input channel that is enabled are displayed with the top line as the programmed Channel IDand the bottom line as the value followed by the programmed units.PATH: ACTUAL VALUES ÖØ METERING ÖØ TRANSDUCER I/O RTD INPUTS Ö RTD INPUT xxActual values for each RTD input channel that is enabled are displayed with the top line as the programmed Channel IDand the bottom line as the value. FLEXELEMENT 1FLEXELEMENT 1OpSig: 0.000 puTable 6–2: FLEXELEMENT™ BASE UNITSBREAKER ARCING AMPS(Brk X Arc Amp A, B, and C) BASE = 2000 kA 2 × cycledcmA BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configuredunder the +IN and –IN inputs.FREQUENCY f BASE = 1 HzFREQUENCY RATE OF CHANGE df/dtBASE = 1 Hz/sPHASE ANGLE ϕBASE = 360 degrees (see the UR angle referencing convention)POWER FACTOR PF BASE = 1.00RTDs BASE = 100°CSENSITIVE DIR POWER(Sns Dir Power)PBASE = maximum value of 3 × V BASE × IBASE for the +IN and –IN inputs of the sourcesconfigured for the sensitive power directional element(s).SOURCE CURRENT I BASE = maximum nominal primary RMS value of the +IN and –IN inputsSOURCE ENERGY(SRC X Positive and NegativeWatthours); (SRC X Positive andNegative Varhours)EBASE = 10000 MWh or MVAh, respectivelySOURCE POWER PBASE = maximum value of V BASE × IBASE for the +IN and –IN inputsSOURCE THD & HARMONICS BASE = 100% of fundamental frequency componentSOURCE VOLTAGE VBASE = maximum nominal primary RMS value of the +IN and –IN inputsSYNCHROCHECK(Max Delta Volts)VBASE = maximum primary RMS value of all the sources related to the +IN and –IN inputs DCMA INPUT xxDCMA INPUT xx0.000 mA RTD INPUT xxRTD INPUT xx-50 °C