4-60 D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUALFRONT PANEL INTERFACE CHAPTER 4: INTERFACES4– Clearing the event records– Clearing the oscillography records– Clearing fault reports– Changing the date and time– Clearing the breaker arcing current– Clearing the data logger– Clearing the user-programmable pushbutton statesTo enter the initial setting or command password:1. Press the MENU key until the SETTINGS header flashes momentarily and the PRODUCT SETUP message appears on thedisplay.2. Press the MESSAGE right arrow until the ACCESS LEVEL message appears on the display.3. Press the MESSAGE down arrow until the CHANGE LOCAL PASSWORDS message appears on the display.4. Press the MESSAGE right arrow until the CHANGE SETTING PASSWORD or CHANGE COMMAND PASSWORD messageappears on the display.5. After the CHANGE...PASSWORD message appears on the display, press the VALUE up or down arrow to change theselection to “Yes.”6. Press the ENTER key and the display prompts you to ENTER NEW PASSWORD.7. Type in a password and press the ENTER key.8. When VERIFY NEW PASSWORD displays, re-type the password and press ENTER.9. When the NEW PASSWORD HAS BEEN STORED message appears, your new Setting (or Command) password is active.4.2.11 Invalid password entryBy default, when an incorrect Command or Setting password has been entered via the front panel three times within fiveminutes, the LOCAL ACCESS DENIED FlexLogic operand is set to “On” and the D30 does not allow settings or command levelaccess via the front panel for five minutes.By default, when an incorrect Command or Setting password has been entered via any external communications interfacethree times within five minutes, the REMOTE ACCESS DENIED FlexLogic operand is set to “ On ” and the D30 does not allowsettings or command access via the any external communications interface for five minutes. The REMOTE ACCESS DENIEDFlexLogic operand is set to “Off” after five minutes for a Command password or 30 minutes for a Settings password.These default settings can be changed in EnerVista under Settings > Product Setup > Security. SECURITY ACCESS LEVEL:Restricted CHANGE LOCAL PASSWORDS CHANGE COMMANDPASSWORD: No CHANGE SETTINGPASSWORD: NoCHANGE SETTINGPASSWORD: NoCHANGE SETTINGPASSWORD: YesENTER NEWPASSWORD: ##########VERIFY NEWPASSWORD: ##########NEW PASSWORDHAS BEEN STORED