20Maintenance and care: Software update and log filesSoftware update and log filesIf you wish to read the log file from the unit without updating the software follow these steps.Step Action1 Insert an empty FAT32 USB memory stick (see section “Formatting to FAT32” on page21).2 After connecting the USB memory stick all collected records will be stored to filedata_log.csv in CSV format. Records won’t be deleted from board so it is possible toget data onto several USB memory sticks.3 When the display has shown the “Log” message and went back to default view, thelog records have been stored succesfully and the USB memory stick can be removed.Data log uses 2KB of backup SRAM (under battery) for data records.Interval for storing records is 3 hours. State change to fail mode also invokes record store.If whole space is filled by record then new one will replace the oldest.Excel column Output text DescriptionTimestamp Time for log since last compressor start sequenceT_amb <-40….100> Temperature of ambient air (-40 = Not conn.)T_amb_int <-40….100> Temperature from internal RH/T sensor (-40 = Not conn.)T_amb_ext <-40….100> Temperature from external RH/T sensor (-40 = Not conn.)T_aux <-40….100> Auxiliary temperature (input) (-40 = Not conn.)T_cond <-40….100> Temperature from condenser (-40 = Not conn.)T_evap1 <-40….100> Temperature from evaporator 1 (-40 = Not conn.)T_evap2 <-40….100> Temperature from evaporator 2 (-40 = Not conn.)T_set <5….34> Setpoint value of desired temperature (Default OFF)RH_amb <0....100> Humidity of ambient air (0 = Not conn.)RH_amb_int <0....100> Humidity from internal RH/T sensor (0 = Not conn.)RH_amb_ext <0....100> Humidity from external RH/T sensor (0 = Not conn.)RH_set <40....99> Humidity set point (Default 60)ExtFanSet <40....99> Extractor fan set point (Default OFF)Service [Blank] Service interval disabled“ENABLED” Service interval enabledMode “SB” Stand-by mode state“STARTUP” Start-up mode state“DEH” Dehumidifying state“ICE” Deicing state“LP” Low-pressure fail mode state“HP” High-pressure fail mode state“SENS” Sensor fail mode state“AMBT” Ambient temperature fail mode“AMBRH” Ambient humidity fail modeError “EVAP” Evaporator sensor Fail“COND” Condenser sensor Fail“AUX” Auxiliary sensor Fail“AMB_INT” Internal ambient sensor error“AMB_EXT” External sensor error (Always shown when no conn.)Reason (For log) “IDLE” Automatically made every 3 hours“ERROR” If an error occurredSensor “SHT31” New sensor type“ChipCap2” Old sensor typeAccess data log/USBData log recordcontent