1052719 • Version 1.0 • 13.08.20191. Remove the front of the unit.Remove the PPI filter and replace with new asper partslist.The new PPI filter must be right up against bothends of the cabinet.Make sure that the hole is furthest away from thefront as shown.2. Release humidity sensor from drip trayand retract it back in to the compressorcompartment.In the compressor compartment pull the sensorthrough the rear hole in the bottom plate.3. Find the compressor compartment cover withthe pre-mounted bracket for the humiditysensor.Dismount the old cover.Mount the new cover and move the sensor tothe front.Note: The bracket ismounted off centerto fit the hole in thePPI filterNote: For CDP/CDF 40 and 50 the filtersmust be cut according to this illustra-tion.1237mm0mm130mm200mm1447mmReplacing RH/T sensor (en)Applies for the following products with serial no. lower than:• CDP/CDF 40: 1809131526904• CDP/CDF 50: 1809241528179• CDP/CDF 70: 1810031531072