PM 1001608 000 06 Device handbook LINAX PQ3000-PQ5000 11/905.2.2 LINAX PQ5000Function Option 1 Option 22 relay outputs 1.1: X1.1 / X1.2 / X1.31.2: X2.1 / X2.2 / X2.32.1: X3.1 / X3.2 / X3.32.2: X4.1 / X4.2 / X4.32 analog outputs 1.1: X2.2(+) / X2. 3(-)1.2: X2.1(+) / X2. 3(-)2.1: X4.2(+) / X4.3 (-)2.2: X4.1(+) / X4.3 (-)4 analog outputs1.1: X2.2(+) / X2.3(-)1.2: X2.1(+) / X2.3(-)1.3: X1.2(+) / X1.3(-)1.4: X1.1(+) / X1.3(-)2.1: X4.2(+) / X4.3(-)2.2: X4.1(+) / X4.3(-)2.3: X3.2(+) / X3.3(-)2.4: X3.1(+) / X3.3(-)4 digital inputs (active)1.1: X1.1(-) / X1.3(+)1.2: X1.2(-) / X1.3(+)1.3: X2.1(-) / X2.3(+)1.4: X2.2(-) / X2.3(+)2.1: X3.1(-) / X3.3(+)2.2: X3.2(-) / X3.3(+)2.3: X4.1(-) / X4.3(+)2.4: X4.2(-) / X4.3(+)4 digital inputs (passive)1.1: X1.1(+) / X1.3(-)1.2: X1.2(+) / X1.3(-)1.3: X2.1(+) / X2.3(-)1.4: X2.2(+) / X2.3(-)2.1: X3.1(+) / X3.3(-)2.2: X3.2(+) / X3.3(-)2.3: X4.1(+) / X4.3(-)2.4: X4.2(+) / X4.3(-)5.3 Possible cross sections and tightening torquesInputs L1(2), L2(5), L3(8), N(11), PE(16), I1(1-3), I2(4-6), I3(7-9), IN(10-12), power supply (13-14)Single wire1 x 0,5 ... 6.0mm 2 or 2 x 0,5 ... 2.5mm 2Multiwire with end splices1 x 0,5 ... 4.0mm 2 or 2 x 0,5 ... 2.5mm 2Tightening torque0.5…0.6Nm resp. 4.42…5.31 lbf inI/O's, relays, RS485 connector (A, B, C/X)Single wire1 x 0.5 ... 2.5mm 2 or 2 x 0.5 ... 1.0mm 2Multiwire with end splices1 x 0.5 ... 2.5mm 2 or 2 x 0.5 ... 1.5mm 2Tightening torque0.5…0.6Nm resp. 4.42…5.31 lbf inYou may have to remove first the plug-in terminals to get access to the screw terminals of the currentinputs.